SSW7000 Medium Voltage Soft Starter
WEGVariable Speed DrivesSSW7000

SSW7000 Medium Voltage Soft Starter

WEG medium voltage soft starter for 2.3–13.8 kV induction and synchronous motors, with integrated bypass, fibre-optic firing and flexible torque control.

Specifications

Series
SSW7000 / SSW7000C
Motor voltage
2.3 – 13.8 kV
Rated current
70 – 600 A
Max. motor power
16,300 HP / 12,200 kW (13.8 kV)
Motor type
Three-phase induction and synchronous
Starting modes
Voltage ramp, current limit, current ramp, pump control, torque control
Protection rating
IP41, IP54 / NEMA 12
Bypass
Vacuum contactor or vacuum circuit breaker
Motor temperature protection
Pt-100, 8 channels
Communication (optional)
DeviceNet, Profibus-DP, EtherNet/IP, Modbus TCP, Modbus RTU
Ambient temperature
Up to 50 °C (current derating above 40 °C)

SSW7000 is a WEG soft starter for starting, stopping and protecting three-phase induction and synchronous medium voltage motors. By controlling the firing angle of anti-parallel thyristors, it reduces the voltage applied to the motor at start, limiting starting current and torque and reducing mechanical shocks and supply voltage dips.

Main and bypass vacuum contactors or vacuum circuit breakers, motor protection and ground fault protection are standard in the cabinet, so no separate protection relay is needed. The power and control sections are fully isolated by fibre-optic firing. WEG's FTC (Flexible Torque Control) technology provides a linear speed ramp according to constant, linear or quadratic load profiles.

Five starting modes are available — voltage ramp, current limit, current ramp, pump control and torque control — together with 8-channel Pt-100 motor temperature protection, a graphic LCD interface, SoftPLC and DeviceNet, Profibus-DP, EtherNet/IP and Modbus options. The series covers 70–600 A rated current and motor power up to 16,300 HP (12,200 kW).

Features

Integrated bypass and protection

Main and bypass vacuum contactors and motor protection are built into the standard cabinet.

Flexible Torque Control (FTC)

A linear speed ramp matched to constant, linear or quadratic loads ensures a smooth start.

Five starting modes

Voltage ramp, current limit, current ramp, pump control and torque control can be selected.

Pump control

A dedicated algorithm reduces water hammer and pressure surges in pipelines.

Fibre-optic isolation

Medium voltage and low voltage compartments are fully separated by fibre-optic firing.

Heavy-duty design

Heatsinks are sized for a real heavy-duty cycle and operation at 50 °C ambient.

Applications

  • Water and wastewater pumping stations
  • Mills, crushers and conveyors in cement and mining
  • Pumps and fans in pulp and paper plants
  • Fans and exhausters in the metals industry
  • Sugar and ethanol plants
  • Marine and offshore applications

Maximum Motor Power by Voltage Class

Supply voltageCurrent rangeMax. motor powerFrame
2,300 V70 – 600 A2,020 kW (2,700 HP)C / B
3,300 V70 – 600 A2,890 kW (3,875 HP)C / B
4,160 V70 – 600 A3,650 kW (4,890 HP)C / B
6,900 V70 – 600 A6,050 kW (8,110 HP)C / B
10,000 V70 – 600 A8,800 kW (11,800 HP)D
11,000 V70 – 600 A9,700 kW (13,000 HP)D
13,200 V70 – 600 A11,650 kW (15,600 HP)D
13,800 V70 – 600 A12,200 kW (16,300 HP)D

Get a quote for this product