W60 Vertical Motor
WEG W60 vertical medium-voltage motor from 1,000 to 7,500 kW and 2.3 to 13.8 kV, developed to drive low-speed vertical centrifugal pumps.
Specifications
- Output
- 1,000–7,500 kW
- Number of poles
- 10–18
- Frame sizes
- 630, 710 and 900
- Voltage
- 2,300–13,800 V
- Frequency
- 50 and 60 Hz
- Degree of protection
- IP24–IP55
- Cooling
- IC01, IC611, IC81W
- Duty
- S1
- Service factor
- 1.00
- Starting
- Direct-on-line (DOL)
- Winding and insulation
- Form-wound VPI, class F
- NDE bearing options
- Angular contact ball, spherical roller thrust or hydrodynamic sleeve bearing
- Temperature sensors
- Pt-100: 2 per phase, 1 per bearing
W60 Vertical is WEG's medium-voltage induction motor line developed specifically to drive low-speed vertical centrifugal pumps. Flexible electrical and mechanical design lets it meet the needs of different applications and sectors, including solutions where the motor must carry external axial loads.
The carbon steel frame gives high rigidity, with the heat exchanger or ventilation box mounted on one side. The cooling circuit is single-sided, with cold air entering at the bottom and hot air leaving at the top. The modular concept allows IC01 (open, self-ventilated), IC611 (air-to-air) and IC81W (air-to-water) cooling. For axial loads such as hydraulic pump thrust, the non-drive-end bearing can be a grease-lubricated angular contact ball bearing, a grease- or oil-lubricated spherical roller thrust bearing or a hydrodynamic sleeve bearing.
Standard equipment includes form-wound VPI windings, class F insulation, an IP66 stator terminal box and Pt-100 sensors, two per phase and one per bearing. Euronorm provides selection support based on pump data and quotations for W60 Vertical.
Features
Made for vertical pumps
Optimised to drive low-speed vertical centrifugal pumps.
Axial load capability
Bearing options handle external axial loads such as hydraulic pump thrust.
Modular cooling
IC01, IC611 and IC81W cooling are offered on the same platform.
Rigid steel frame
The carbon steel frame is durable in harsh and corrosive environments.
Standard monitoring
Pt-100 sensors, two per phase and one per bearing, monitor temperatures.
Applications
- Vertical centrifugal pumps
- Water and wastewater plants
- Power generation plants
- Oil, gas and mining facilities
Get a quote for this product